1840 1 0 P 0 4 8 1 Cable Temperature Sensors QAH11... The sensors are for use in HVAC plants to acquire the temperature in fan coil units. Because of their insulation, the sensors are especially suited for use with controllers whose sensor signal input are not galvanically separated from the AC 230 V mains.
The sensors are used as: (cid:120) return air temperature sensors (cid:120) changeover sensors Type reference Features QAH11 QAH11.1 Cable temperature sensor with connectors 2.8 x 0,8 mm
Cable temperature sensor with ferrules Accessories Name Changeover mounting kit Type reference ARG86.3 Ordering and delivery When ordering, please give name and type reference of sensor and/or changeover mounting kit. The sensor is supplied without the changeover mounting kit.
The sensor acquires the air or medium temperature by means of its NTC sensing element. The resistance value changes according to the temperature to be acquired. It is available for further handling by a suitable controller.
Building Technologies Use Type summary Functions CM1N1840en 2014-07-30 Mechanical design Mounting notes Disposal Technical data Functional data Protection data Electrical connections
Directives and Standards Environmental compatibility Weight Internal diagram The sensor consists of a two-wire cable with NTC sensing element and connectors. The changeover mounting kit, which is available as an accessory item, is used for fitting the sensor to a pipe (12...16 mm dia.).
The sensors should be fitted where it can best acquire the temperature to be meas-ured. When fitting to a pipe, the pipe must not be lagged where the sensor is located.
The devices are considered electronics devices for disposal in terms of European Directive 2012/19/EU and may not be disposed of as domestic waste. (cid:120) Dispose of the device via the channels provided for this purpose. (cid:120) Comply with all local and currently applicable laws and regulations.
Operating range Sensing element Time constant in static air Accuracy at 25 °C Type of measurement and output Protection class Length of measuring lead Type of cable Length Electrical connection QAH11 QAH11.1 Product standard
(cid:16) 20...(cid:14) 70 °C 1) NTC (3 k(cid:58) at 25 °C) 1.5 min (cid:114) 0.3 K passive II according to EN 60730-1 approx. 2.5 m H03VV-F2 2 x 0.75 black 2.5 m
plug connectors 2.8 x 0.8 mm ferrules EN 60730-1 Automatic electrical controls for household and similar use The product environmental declaration CE1E17012) contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal).
incl. packaging 0.07 kg 1) If the connecting cable is not fixed, only (cid:16) 5 °C is permitted as the low temperature limit. 2) The documents can be downloaded from http://siemens.com/bt/download.
NTC 1 0 G 0 4 8 1 Resistance characteristic NTC 3 k(cid:58) at 25 °C Temp. in °C (cid:16)20 (cid:16)15 (cid:16)10 (cid:16)5 0 (cid:14)5 (cid:14)10 (cid:14)15 (cid:14)20
(cid:14)25 Resist. in (cid:58) 29'751 22'257 16'815 12'825 9'867 7'656 5'991 4'722 3'750 3'000 Temp. in °C (cid:14)30 (cid:14)35 (cid:14)40 (cid:14)45 (cid:14)50
(cid:14)55 (cid:14)60 (cid:14)65 (cid:14)70 Resist. in (cid:58) 2'416 1'958 1'597 1'310 1'081 897.0 747.9 627.0 528.0 2/3 Siemens Building Technologies Cable temperature sensors QAH11...
CM1N1840en 2014-07-30 Dimensions (in mm) QAH11, QAH11.1 7, 7ø5ø7ø26 7, 7ø5ø1 0 M 0 4 8 1 7ø60 26 2500 2500 3 0 M 0 4 8 1 60 ARG86.3 36 1 ca. 12...16 2 0 M 0 4 8 1
3/3 (cid:164) 2000 - 2014 Siemens Switzerland Ltd Siemens Building Technologies Cable temperature sensors QAH11... Subject to change CM1N1840de 2014-07-30