OpenAirTM Actuators for Fire and Smoke Protection Dampers GRA126.1E/... GRA326.1E/...• Electric motor driven actuators for 2-position control, nominal torque 4 Nm, with spring return to failsafe position, mechanically adjustable span between 0...90°, prewired with 0.9 m long connecting cables
• Operating voltage AC 24 V / DC 24…48 V or AC 230 V• Optional temperature monitoring unit with 3 thermal cutouts (72 °C) and test button• Fixed auxiliary switches for switching points 5° and 80°• Rigid connection between actuator and damper shaft
For the control of fire and smoke protection dampers.• Nominal torque of 4 Nm for damper surfaces up to about 0.6 m2 (friction-dependent)• In fire protection sections of plant where, in the event the thermal fuse cuts out at a duct or ambient temperature of 72 °C, or in case of a power failure, the actuator
must travel to the failsafe position (zero position) Use A6V10888424en 2016-12-05 Building Technologies Functions Basic functions Rotary movement Behavior in the event the damper is blocked
Position indication Manual adjustment when actuator is dead Failsafe function• If the thermal fuse cuts out at a duct or ambient temperature of 72 °C (Optional:
• Direction of rotation (clockwise or counterclockwise) determined by the way the actuator is mounted on the damper shaft• When operating voltage is applied, the actuator travels toward the 90° position
95 °C), the return spring drives the actuator to the failsafe position (0°)• In the event of a power failure or if the operating voltage is turned off, the return
spring drives the actuator to the failsafe position (0°) The actuator is equipped with an automatic switch-off mechanism. The position indicator located on the shaft adapter shows the rotational angle position of the damper blade.
• When dead, the actuator can be driven to any angular position using a hex wrench and can then be secured with a screwdriver• The actuator returns to its zero position when mechanically delocked with a hex
wrench (turning toward "90° - opening") or by applying power for a short moment Rigid connection Square shafts 10 x 10 or 12 x 12 mm. Type summary Operating voltage
AC 24 V DC 24…48 V Delivery Auxiliary switches Fixed switching points at 5° and 80°AC 230 V Fixed switching points at 5° and 80°With temperature monitoring unit
GRA126.1E/T10 GRA126.1E/T12 GRA326.1E/T10 GRA326.1E/T12 Without temperature monitoring unit GRA126.1E/10 GRA126.1E/12 GRA326.1E/10 GRA326.1E/12 Due to the mounting choices depending on the direction of rotation and the shaft length, shaft adapter with position indicator and other mounting accessories are
shipped unassembled together with the actuator. Connecting cables The actuators come with 0.9 m long prewired connecting cables. The cable length to the ready fitted temperature monitoring unit is 0.9 m.
Accessories Designation Type reference Data sheet / mounting instruction Duct tip to temperature monotoring unit ASK79.4 / 72 °C ASK79.5 / 95 °C A6V10890425 / M4610
Equipment combinations The damper actuators can be used with all types of controllers having a 2-position output and delivering a switching voltage of AC 24 V / DC 24…48 V or AC 230 V.
2/12 Siemens Building Technologies Actuators for fire and smoke protection dampers GRA126.1E/.., GRA326.1E/.. A6V10888424en 2016-12-05 Technical design Drive motor
Spring return mechanism in the event of power failure Mechanical design Basic components Housing Gear train Spring preload The brushless DC motor ensures accurate speed control, torque monitoring for protecting the actuator and the air damper, and provides a reliable failsafe function.
Mechanical spring ensure the failsafe function. Robust, lightweight all metal housing made from die-cast aluminium which guarantees a long service life even under extreme environmental conditions.
Maintenance- and noise-free gear train with stall and overload protection for the life of the actuator. The spring has a factory-set preload of 5° to ensure tight shutoff for the fire and smoke protection dampers.
Manual adjustment A hole with a screw in the center of the actuator allows manual setting of the gears. A hex wrench is supplied. Mounting bracket A perforated bracket with pin available, depending on the way the actuator is fixed.
Electrical connection All actuators come with prewired 0.9 m long connecting cables. Note The actuators can be mounted on either side depending on the required direction of rotation. All setting and operating elements are available on both sides of the actuator.
Auxiliary switches Fixed switching points at 5° and 80°. Temperature monitoring unit Use The temperature monitoring unit is ready connected to the actuator and is used for forced control of motorized fire and smoke protection dampers should excessive temperatures occur.
Mode of operation The temperature monitoring unit contains 3 thermal fuses, two for monitoring the duct temperature and 1 for the ambient temperature. If the temperature at any of these fuses exceeds the level of 72 °C (Optional: 95 °C), the power supply will be irreversibly cut. As a result, the return spring will drive the actuator to the failsafe position. A test button
is integrated for making functional checks. When pressed, the current path will be cut. LED functions (cid:154) Red = Operating voltage OK. Thermo sensor defect
(cid:154) Green = Operating voltage OK Thermo sensor OK (cid:152) Dark = No operating voltage Siemens Building Technologies Actuators for fire and smoke protection dampers GRA126.1E/.., GRA326.1E/..
3/12 A6V10888424en 2016-12-05 Refer to "Technical design" and "Commissioning notes" in this Data Sheet. Setting and operating elements 1 2 3 4 5 6 7 8 9 10 11 12
13 14 Housing Angle of rotation scale 0°...90°Hexagon socket for manual override Connecting cable for power supply Connecting cable for auxiliary switches Stop shaft for gear train
Position indicator Shaft adapter Locking ring for shaft adapter Adapter for position indicator Temperature monitoring unit Pin Mounting bracket Hex wrench for manual override
Arrangement for shaft adapters 8 9 10 7 4/12 Siemens Building Technologies Actuators for fire and smoke protection dampers GRA126.1E/.., GRA326.1E/.. A6V10888424en 2016-12-05
Engineering notes STOP Correct use Power supply AC 24 V DC 24…48 V Power supply AC 230 V Parallel connection of actuators Sizing transformers for AC 24 V Wiring and commissioning
Mounting notes Mounting instructions The basic system data for the control systems in use contain all engineering notes. Read all the engineering notes before mounting, wiring and commissioning the damper actuator and pay special attention to all safety instructions.
These damper actuators must be used on applications as described in the basic system data documents for the relevant control systems. Additionally, all actuator-specific features and rules must be observed as described in the brief description on the front page of this Data Sheet (bold print) and in "Use", "Engineering notes", and
"Technical data". All paragraphs marked with the special warning triangle as illustrated on the left contain additional safety instructions and limitations that must be observed under any circum-stances to avoid physical injuries or damage to equipment.
These actuators must be used with safety extra low-voltage (SELV) or protection by extra low-voltage (PELV) in accordance with HD 384. The actuators are double-insulated and do not provide a connection for protective ground.
Auxiliary switches“A”, “B”Use either mains voltage or safety extra low-voltage for auxiliary switches “A” and“B”. Do not mix the 2 for operation. Operation with different phases is not permitted.
Warning, maintenance Do not open the actuator!The actuator is maintenance-free. Maintenance work may only be carried out by the manufacturer. Electric parallel connection of the same types of actuator is permitted provided operating voltage is within the required tolerance. Voltage drops on the supply lines
must be taken into consideration• Use safety isolating transformers with double insulation conforming to EN 60 742. The transformers must be suited for 100 % duty• Observe all local safety rules and regulations relating to the sizing and protection of
• Determine the transformer’s size by adding up the power consumption in VA of all actuators used transformers Refer to "Commissioning notes" and "Internal diagram" as well as to the plant diagram.
For detailed information on the correct preparation of the actuator, refer to Mounting Instructions GRA…1E/.. A6V10890425. The actuator must be fitted to the fire and smoke protection damper as specified by the OEM. Shaft adapter and other accessory items come unassembled, since their assembly depends on the direction of rotation
a