2-port control ball valves, PN 25, with internally threaded connection ACVATIX™VAI51.. For use in heating, ventilation, and air conditioning plants as control or shutoff
valve. In closed circuits.● Ball valve body made of brass, ball and stem made of stainless steel● DN 15...50● kvs 4...63 m3/h● Connections with internal threading Rp per ISO 7-1● Rotational angle 90°● Can be used with electromotorized rotary actuators GQD..9A, GMA..9E with
spring return and GSD161.9A, GDB..9E, GLD161.9E, GLB..9E without spring return● For applications with auxiliary functions (e.g. auxiliary switch, potentiometer, see Applications with auxiliary functions), can also be combined with standard rotary actuators
A6V12170194_en--_a 2021-05-26 Smart Infrastructure Features● Moderately price: Optimized flow rates mean smaller ball valves can be selected. Low torque means you can combine them with small, less expensive rotary actuators.
● High life expectancy: Maintenance-free construction, also thanks to low friction stem and polished ball made of stainless steel.● Simple mounting: The brackets, pre-mounted on the actuators, means you can mount them on the ball valves without tools.
Technical design Design Housing Seat 5 Marble 1 3 7 9 Slide clutch Flow plate Internally threaded connection 2 4 6 8 O-ring seal Stem, squared O-ring seal 2 Siemens Smart Infrastructure
A6V12170194_en--_a 2021-05-26 Sizing Flow diagram:ΔpmaxΔpmax for VAI51.., for details, see table on Equipment combinations= Maximum permissible differential pressure over the ball valve, valid for the entire positioning range of the ball valve rotary actuator unit; if low noise operation is desired, we recommend a maximum permissible differential
pressure of 200 kPaΔpv100= Differential pressure over the fully opened ball valve and over the control path at a volume flow V100⩒100= Volume flow through the fully opened ball valve
100 kPa= 1 bar ≈ 10 mWS 1 m3/h= 0.278 l/s water at 20 °C Siemens Smart Infrastructure 3 A6V12170194_en--_a 2021-05-26 Ball valve characteristic curve Flow rate kv / kvs
Rotational angle Flow characteristics 0…100 %-> A ─ AB equal percentage, ngl = 3 per VDI / VDE 2173 Cavitation Cavitation increases wear and tear of the ball and seat and results in unwanted noise. Cavitation can be prevented by not exceeding the differential pressures as per the flow diagram and maintaining the static pressures depicted below.
Δpmax= Differential pressure at a nearly closed ball valve to largely avoid cavitation P1 P3 Mϑ= Static pressure at the ball valve inlet= Static pressure at the ball valve outlet
Pump Water temperature Example with hot water: Pressure p1 at ball valve inlet: 500 kPa (5 bar) Water temperature: 120 °C 4 Siemens Smart Infrastructure A6V12170194_en--_a 2021-05-26
The above diagram clearly indicates that the maximum permissible differential pressure isΔpmax → 200 kPa (2 bar) at a nearly closed ball valve. Note on chilled water applications To prevent cavitation in chilled water circuits, sufficient counter pressure must be supplied to the ball valve outlet, e.g. using an additional butterfly valve downstream of the ball valve.
Maximum permissible differential pressure over the ball valve: See 80 °C curve in the above diagram. Operating pressure and operating temperature Liquids: Operating pressure [bar]
Operating temperature [°C]Operating pressure and medium temperature per IS0 7005 (Observe all local and applicable laws). Siemens Smart Infrastructure 5 A6V12170194_en--_a 2021-05-26
Type summary Type Stock number DN Sv kvs[m3/h]4.0 6.3 6.3 10 10 16 16 25 25 40 40 63 15 20 25 32 40 50> 100 VAI51.15-4 S55230-V203 VAI51.15-6.3 S55230-V204 VAI51.20-6.3
S55230-V205 VAI51.20-10 VAI51.25-10 VAI51.25-16 VAI51.32-16 VAI51.32-25 VAI51.40-25 VAI51.40-40 VAI51.50-40 VAI51.50-63 S55230-V206 S55230-V207 S55230-V208 S55230-V209
S55230-V210 S55230-V211 S55230-V212 S55230-V213 S55230-V214 DN kvs Sv kvr====Nominal size Rangeability kvs / kvr Flow nominal value for chilled water (5…30 °C) through a fully opened ball valve at a differential pressure of 100 kPa (1 bar)
The smallest kv value at which the characteristic curve tolerances can be maintained at a differential pressure of 100 kPa (1 bar) 6 Siemens Smart Infrastructure
A6V12170194_en--_a 2021-05-26 Equipment combinations Type GQD..9A GSD161.9A GDB..9E GMA..9E GLD161.9E GLB..9EΔpmax Δps Δpmax Δps Δpmax Δps Δpmax Δps Δpmax Δps Δpmax
Δps Rotary actuators[kPa]1400 1400 350 350 350 1400 1400 1400 1400 600 600────────────────────────────────────350 350 350 1000 1000 1000 800 400 800 400 800 600
= Maximum permissible differential pressure over the ball valve control path, valid for the entire positioning range of the ball valve rotary actuator unit; if low noise operation is desired, we recommend a maximum permissible differential pressure of ≤ 200 kPa
Δps= Maximum permissible differential pressure (closing pressure) at which the ball valve rotary actuator unit securely closes against the pressure Overview of rotary actuators for ball valves
Type 1) Operating voltage Positioning Spring return Data sheet Signal Time Function Time AC/DC 24 V 30/15 s 2) Yes 15 s N4659 AC/DC 24 V DC 0…10 V 30 s A6V10636056
3-position DC 0…10 V 2 or 3 point 0/2…10 V 3-position DC 0…10 V 150 s AC/DC 24 V AC 100-240 V AC/DC 24 V AC/DC 24 V GLD161.9E AC 24 V / DC 24…48 V DC 0/2…10 V 30 s
──A6V11171770 90/15 s 2) Yes 15 s N4658─----─------A6V10636150 A6V10636203 A6V107255318 A6V10938035 AC/DC 24 V AC 100-240 V 2 or 3 point 150 s AC/DC 24 V 0/2…10 V
GDB111.9E/KN GLB111.9E/MO AC 24 V AC 24 V KNX-TP 150/120 s Modbus RTU 150/120 s 1) Actuator type: Electromotive 2) Open/close Ball valve VAI51.15-4 VAI51.15-6.3
VAI51.20-6.3 VAI51.20-10 VAI51.25-10 VAI51.25-16 VAI51.32-16 VAI51.32-25 VAI51.40-25 VAI51.40-40 VAI51.50-40 VAI51.50-63Δpmax GQD131.9A GQD161.9A GSD161.9A GDB141.9E
GDB341.9E GDB161.9E GMA131.9E GMA161.9E GLB141.9E GLB341.9E GLB161.9E Siemens Smart Infrastructure 7 A6V12170194_en--_a 2021-05-26 Notes Safety Ordering Please indicate material, article type, order text, and quantity; example:
Material Article type Order text VAI51.25-16 VAI51.25-16 Open/close ball valve internally threaded, 2-Port GLB161.9E GLB161.9E Actuator for ball valve, NSR Quantity
2 2 Delivery Ball valves, rotary actuators, and mounting kits are not assembled and are delivered in individual packaging. Applications with auxiliary functions A standard actuator with corresponding functionality can be used if a ball valve application requires a rotary actuator with auxiliary functions (e.g. auxiliary switch or potentiometer). In
this case, mounting kit ASK77.x is required in addition to the rotary actuator. Follow the mounting instructions when mounting. Rotary actuator Options Order text: Mounting kit
GMA1..1E (with spring return) GDB..1E/GLB..1E (without spring return) GQD..1A (with spring return) GSD..1A 1) (without spring return) Potentiometer, auxiliary switch
ASK77.2 Accessory Kit BV for GMA1..1E Potentiometer, auxiliary switch ASK77.3 Accessory Kit BV for GDB..1E/GLB..1E Auxiliary switch ASK77.5 Accessory Kit BV for GQD..1A
Auxiliary switch ASK77.5 Accessory Kit BV for GSD..1A Note: 1) GSD141.1A (S55499-D281) and GSD341.1A (S55499-D282) are not compatible with ball valves. Product documentation
Related documents such as environmental declarations, CE declarations, etc., can be downloaded at the following Internet address: http://siemens.com/bt/download
DANGER There is a risk to operating personnel and device when working on the unit Failure to comply with these safety notes can result in personal injury and damage to property from pipe pressure, electrical voltage, or device in operation.
Note the following when servicing a ball valve/rotary actuator:● Switch off both pump and operating voltage.● Close shutoff valves.● Release pressure in