内容提要
以下文字自动提取自资料正文,排版可能与原件不同,完整参数请以文件为准。
ACVATIX TM SAS.. Electromotoric actuators for stroke valves Electromotoric actuators with 5.5 mm stroke and 400 N positioning force (cid:4288) SAS31.. Operating voltage AC 230 V, 3-position control signal (cid:4288) SAS61.. Operating voltage AC 24 V / DC 24 V, position signal DC 0...10 V / DC 4...20 mA / 0...1000 (cid:726)
(cid:4288) SAS81.. Operating voltage AC/DC 24 V, 3-position control signal (cid:4288) For direct mounting on valves; no adjustments required (cid:4288) Manual adjuster, position indicator and status indication per LED (cid:4288) Optional functions with auxiliary switch
CE1N4581en 2016-01-13 Building Technologies Application Functions For the operation of Siemens 2-port and 3-port valves: (cid:4288) Types V..G44.., VVG55 and VVG549.. (cid:4288) 5.5 mm stroke As control or shutoff valves in heating and ventilation plants.
In conjunction with the ASK30 mounting kit, the former Landis & Gyr-valves with 4 mm or 5.5 mm stroke can also be operated: X3i.., VVG45.., VXG45.., VXG46.., VVI51…
Function Description 3-position control Modulating control A 3-position signal drives the actuator via connection terminals Y1 or Y2. The desired position is transmitted to the valve.
The modulating positioning signal drives the actuator steplessly. The positioning signal range (DC 0...10 V / DC 4...20 mA / 0...1000 (cid:726)) corresponds in a linear manner to the positioning range (fully closed...fully open, or 0...100 % stroke).
Type SAS31.. SAS81.. SAS61.. Positioning signal and characteristic changeover Setting the DIL switches. Factory setting SAS..: (cid:120) (cid:120) Characteristic curve : log = Equal percentage (switch at"OFF")
Positioning signal: DC 0...10 V (switch at "OFF") Position feedback U Signal, returned to acquire the position via an input. Calibration Conduct during initial commissioning. The actuator deploys to the top and bottom end position; measured values are saved.
Detection of valve seat Actuators have power-dependent seat detection. After calibration, the exact valve stroke is filed in the actuator’s memory. Foreign body protection
After detection of clogging, 3 attempts are made to overcome clogging. If the attempts made are unsuccessful, the actuator continues to follow the positioning signal within the restricted range only (LED continues to blink red).
Forced control Z (Z mode) Forced control serves for overriding automatic mode and is implemented in the structure. 2 Siemens Building Technologies CE1N4581en 2016-01-13
Types Type Stock no. Operating voltage Positioning signal Power consumption Posit. time Spring return function/time Manual adjust-ment Position feedback Remark SAS31.00
S55158-A106 AC 230 V 3-position 2,8 / 2,4 VA 5) 120 s No Yes-1) 3) SAS31.03 S55158-A107 SAS31.50 S55158-A108 3,5 / 2,9 VA 5) 30 s 3,5 / 2,9 VA 5) 120 s Yes / <28 s
No SAS31.53 S55158-A109 5,5 / 3,8 VA 5) 30 s Yes / <14 s SAS61.03 S55158-A100 AC/DC 24 V DC 0…10 V 5,3 / 4,5 VA 5) 30 s No Yes DC 0…10 V 4) SAS61.03U S55158-A100-A100
SAS61.33 S55158-A101 SAS61.33U S55158-A101-A100 SAS61.53 S55158-A102 SAS81.03 S55158-A104 SAS81.03U S55158-A104-A100 SAS81.33 S55158-A105 SAS81.33U S55158-A105-A100
6) 6) Yes / <14 s 6) DC 4…20 mA 0…1000 (cid:726) 5,3 / 4,5 VA 5) 5,9 / 4.8 VA 5) 5,9 / 4.8 VA 5) 5,8 / 5,0 VA 5) 2,5 / 2,1 VA 5) 30 s 2,5 / 2,1 VA 5) 3,4 / 2,4 VA 5)
3,4 / 2,4 VA 5) Yes / <14 s 6) SAS81.00 S55158-A103 AC/DC 24 V 3-position 2,2 / 2,0 VA 5) 120 s No No Yes-1) 2) 1) 2) 1) 1) 1) 2) 1) 2) 1) Cable gland: M16, M20 (ISO50262)
4) Approbation: CE and UL (only 24 V) 2) Cable gland ½" (UL514C) 5) Second value: Power consumption at normal position 3) Approbation: CE 6) Spring return time at low temperature is slightly longer
Delivery Actuator, valve and accessories are packed and supplied as separate items. Accessories Electric accessories Auxiliary switch ASC10.51 Mechanical accessories
Weather shield ASK39.2 4 1 Z 1 4 0 4 5 2 Z 1 4 0 4 Ordering (Example) Type SAS31.00 Stock no. Designation S55158-A106 Actuator Quantity 1+ auxiliary components (connections, auxiliary switches(cid:4824)
Siemens Building Technologies 3 CE1N4581en 2016-01-13 Spare parts Stock no. S55845-Z180 Description Type ASQ1: Housing cover with screws and light guides as component, without laser labeling
Compatibility VVG44.. (2-port) VXG44.. (3-port) DN G Valves PN16 Medium: 1…120 °C VVG44.15-..1) VXG44.15-..1) G 1 B 0,25 / 0,4 / 0,63 kvs[m3/h]1 / 1,6 2,5 / 4 6,3
10 16 25 kvs[m3/h]0,25 0,4 0,63 1,0 1,6 2,5 4,0 6,3 6 0 Z 1 4 0 4 Actuators SAS.. Actuators SAS.. 1) (cid:3545)ps[kPa]1600 725 400 750 400 250 125 (cid:3545)ps[kPa]
2500 2500 2500 1500 1500 1500 1600 1600 (cid:3545)ps[kPa]2500 2000 1000 800 (cid:3545)pmax[kPa]400 400 400 400 400 250 125 (cid:3545)pmax[kPa]1200 1200 1200 1200
1200 1200 1200 1200 (cid:3545)pmax[kPa]1200 1200 1000 800[Inch]G 1 B G 1 B 15 15 15 20 G 1 ¼ B 25 G 1 ½ B 32 G 2 B 40 G 2 ¼ B DN G[Inch]G ¾ B G ¾ B G ¾ B G ¾ B G ¾ B
G ¾ B G 1 B G 1 ¼ B 15 15 15 15 15 15 20 25 15 15 20 Actuators SAS.. G ¾ B 0,25 / 0,4 / 0,63 DN G[Inch]G ¾ B G 1 B 25 G 1 ¼ B kvs[m3/h]1 / 1,6 / 2,5 4 6,3 VVG44.15-..1)
VVG44.15-..1) VXG44.15-..1) VXG44.15-..1) VVG44.20-6.3 VXG44.20-6.3 VVG44.25-10 VXG44.25-10 VVG44.32-16 VVG44.40-25 VXG44.32-16 VXG44.40-25 Ventile PN25 VVG549.. (2-port)
Medium: 1…130 °C VVG549.15-0.25 VVG549.15-0.4 VVG549.15-0.63 VVG549.15-1 VVG549.15-1.6 VVG549.15-2.5 Pressure compensated VVG549.20-4K VVG549.25-6.3K Valves PN25
VVG55.. (2-port) 1) Medium: 1…130 °C VVG55.15-..2) VVG55.15-..2) VVG55.20-4 VVG55.25-6.3 2) Use = kvs value 1) SAS.. combined with VVG549: DIL switch setting change to linear (Factory setting = log).
1) VVG55 will be replaced by VVG549 as of 2017-01-01. 4 Siemens Building Technologies CE1N4581en 2016-01-13 Product documentation Name Topic Document ID SAS.., SAT.. actuators for valves
Detailed information about the SAS.. actuators CE1P4041en Basic documentation Related documents such as environmental declarations, CE declarations, etc., can be downloaded at the following Internet address: http://siemens.com/bt/download
Siemens Building Technologies 5 CE1N4581en 2016-01-13 Notes Safety Engineering CAUTION National safety regulations Failure to comply with national safety regulations may result in personal injury and property damage.
(cid:4288) Observe national provisions and comply with the appropriate safety regulations. SAS31.. and SAS81.. 3-position actuators must have their own controller, see "Connection diagrams".
SAS61.. Up to 10 actuators can drive in parallel on a controller output with a rating of 1 mA. Modulating actuators have an input impedance of 100 k(cid:726). Installation
Mounting positions Indoor use Outdoor use 1) 1) Requires the weather shield ASK39.2. Degree of protection of housing IP54 remains unchanged. Maintenance The SAS.. actuators are maintenance-free. Mounting: (cid:4288) Do not touch the valve coupling if the components (valve/pipes) are hot If necessary, disconnect electrical connections from the terminals
(cid:4288) The actuator must be correctly fitted to the valve before recommissioning. 6 Siemens Building Technologies CE1N4581en 2016-01-13 Disposal Warranty The device is considered an electronics device for disposal in terms of European Directive 2012/19/EU and may not be disposed of as domestic garbage.
(cid:4288) Dispose of the device through channels provided for this purpose. (cid:4288) Comply with all local and currently applicable laws and regulations. Technical data on specific applications are valid only together with Siemens products listed under "Equipment combinations". Siemens rejects any and all warranties in the event that
third-party products are used. Note When using the actuators in connection with valves of other manufacture, correct functioning must be ensured by the user, and Siemens will assume no responsibility.
Technical data Power supply Operating voltage SAS31.. SAS61.. SAS81.. Frequency External supply line protection (EU) SAS.. AC 230 V (±15 %) AC 24 V ± 20 % / DC 24 V +20 % / -15 % (cid:3259)
or AC 24 V class 2 (US) AC/DC 24 V ± 20 % (cid:3259)or AC 24 V class 2 (US) Fuse slow 6 A…10 A or fuse switch max. 13 A, release characteristic B,C,D per EN 60898 power source with current limitation of
45…65 Hz max. 10 A 120 s 30 s 400 N 5.5 mm 1…130 °C Power consumption at 50 Hz See "Type summary"; stem retracts/extends Function data Positioning time for nominal stroke
Positioning force Nominal stroke Permissible medium temperature Signal inputs SAS..0 SAS..3 / SAS..3U valve fitted Y positioning signal SAS31../SAS81.. 3-position
SAS61.. DC 0…10 V / D