内容提要
以下文字自动提取自资料正文,排版可能与原件不同,完整参数请以文件为准。
Electromotoric actuator SSF161.05HF, SSB161.05HF, SSC161.05HF, SSC161.35HF For globe/control valves VVP45.., VXP45.., VMP45.., VVP47.., VXP47.., VMP47.. in zone and room applications
● Operating voltage AC/DC 24 V, positioning signal DC 0...10 V● Self calibrating to the valve stroke● Direct mounting with coupling nut, no tools required● Manually adjustable, position and actuator motion indication (LED)● SSF161.05HF, SSB161.05HF: Positioning force 200 N● SSC161.05HF, SSC161.35HF: Positioning force 300 N
● Parallel operation of multiple actuators possible● Removable cable, standard length 1.5 m Optionally as accessories: Cable length 3 m and 6 m, halogen-free cables
● SSC161.35HF with electrical fail-safe function A6V12681511_en--_b 2023-05-17 Smart Infrastructure Use Typically in chilled ceiling, VAV and fan coil unit applications SSF…:● For 2-port small valves and 3-port small valves VVP47..; VXP47.. and VMP47..● For retrofitting the small valves 2W..K.., 3W.., 4W..with adapter AL100 SSB..
● For 2-port valves and 3-port valves VVP45..; VXP45.. and VMP45.. up to Kvs 6.3 Typically in chilled ceiling, VAV, fan coil unit, heating and cooling coils as well as pre-control loop applications SSC…
● For 2-port valves and 3-port valves VVP45..; VXP45.. and VMP45..● For Landis & Gyr valves VVG45.., VXG45.. and X3i with adapter ASK30 Technical design DC 0…10 V positioning signal
When the actuator is driven by DC 0…10 V positioning signal, it produces a stroke, which is transmitted to the valve stem.● The valve opens / closes in proportion to the
positioning signal at Y.● At DC 0 V, actuator stem is retracted, the normally closed valve is fully closed.● When there is no operating voltage, the actuator maintains its current position.
● The actuator provides a position feedback signal U of DC 0…10 V proportional to the calibrated valve stroke. Y = Positioning signal Y [V]H = Percentage of calibrated valve stroke U = Position feedback signal
LED indication Status Variants SSF161.05HF, SSB161.05HF, SSC161.05HF, SSC161.35HF LED indication patterns Stroke movement: Stem retracting Flashing green in sequence: LED1-->LED2-->LED3 (500 ms each)
Stroke movement: Stem extending Flashing green in sequence: LED3-->LED2-->LED1 (500 ms each) Stem stays in position Fail-safe*Calibration Error**At H0 - H40: Constant green (LED3)
At H40 - H60: Constant green (LED2) At H60 - H100: Constant green (LED1) Flashing red (LED2): 500 ms on, 500 ms off Flashing green (LED2): 100 ms on, 100 ms off
Constant red (LED2) Manual operation Flashing green/red alternatively (LED2): Green 500 ms, red 500 ms Super-cap initial charging*Constant green & red simultaneously (LED2): Constant orange
* Only available for SSC161.35HF Siemens Smart Infrastructure 2 A6V12681511_en--_b 2023-05-17** Error caused by mechanical jam or calibration failure. Calibration through resetting the operating voltage required.
Type summary Accessories Type Stock number Operating voltage Running speed Nominal force Stroke range Positioning signal Actuator characte ristic Cable length Coupling nut
SSF161.05HF S55180-A131 AC/DC 24 V 5 s/mm 200 N 1.2...6.5 mm DC 0…10 V Linear 1.5 m M30×1.5, plastic SSB161.05HF S55180-A134 AC/DC 24 V 5 s/mm 200 N 1.2...6.5 mm DC 0…10 V Linear
1.5 m ¾”, plastic SSC161.05HF S55155-A101 AC/DC 24 V 5 s/mm 300 N 1.2...6.5 mm DC 0…10 V Linear 1.5 m ¾”, metal SSC161.35HF S55155-A102 AC/DC 24 V 5 s/mm 300 N 1.2...6.5 mm DC 0…10 V Linear
1.5 m ¾”, metal Type Stock number Number of wires and cross section [mm2] Voltage [V] Cable length [m]ASY161L15 S55845-Z266 5x0.34 ASY161L30 S55845-Z267 5x0.34 ASY161L60
S55845-Z268 5x0.34 ASY161L15HF S55845-Z269 5x0.34 halogen free ASY161L30HF S55845-Z270 5x0.34 halogen free ASY161L60HF S55845-Z271 5x0.34 halogen free When ordering, specify both type and quantity. Example:
24 24 24 24 24 24 1.5 1.5 3 6 3 6 Type Stock number Designation Quantity SSF161.05HF S55180-A131 Electromotoric actuator 2 Ordering Delivery Valves and actuators must be ordered separately. For easier valve assembly, actuators ordered separately have the actuator stem fully retracted.
Equipment combinations SSF161.05HF combinable with the following valves Type reference Valve type VVP47.. 2-port valves VXP47.. 3-port valves VMP47.. 3-port valves with T-bypass
2W…K…1)2-port valves 3-port valves 3-port valves with T-bypass 3W…1)4W…1)Others Kvs [m3/h]PN class Data sheet 0.25…4.0 PN 16 N4847 0.25…4.0 0.25…2.5 0.6…2.5 0.6…4.0
0.6…2.5 N4847 N4847 N4846 N4846 N4846 Valves (M30x1.5) from other manufacturers, without adapter---Siemens Smart Infrastructure 3 A6V12681511_en--_b 2023-05-17 1)With assembly adapter AL100
SSB161.05HF combinable with the following valves Type reference Valve type Kvs [m3/h]PN class Data sheet VVP45.. 2-port valves 0.25…6.3 PN 16 N4845 VVP45..S 2-port valves, for compression fittings
VXP45.. 3-port valves VMP45.. 3-port valves with T-bypass 0.63…2.5 0.25…6.3 0.25…4.0 VMP45..S 3-port valves with T-bypass, for compression fittings 0.63…2.5 N4854
N4845 N4845 N4854 Others Valves (¾”) from other manufacturers, without adapter---Note: SSB.. Actuators are not suitable for valves VVP45..N. SSC161.05HF, SSC161.35HF combinable with the following valves
Valves (¾”) from other manufacturers, without adapter---Type reference Valve type VVP45.. 2-port valves VVP45..N 2-port valves VXP45.. 3-port valves VVG45..1) 2-port valves
VXG45..1) 3-port valves 3-port valves X3i..1) Others VMP45.. 3-port valve with T-bypass 1)With assembly adapter ASK30 Note: To ensure trouble-free operation of third-party valves with the actuator, the valves must satisfy the following requirements:● Threaded connections with coupling nut:
– SSF161.05HF: M30×1.5– SSC161.05HF, SSC161.35HF, SSB161.05HF:¾”● Nominal force:– SSF161.05HF, SSB161.05HF: 200 N– SSC161.05HF, SSC161.35HF: 300 N● Open dimension X ≥ 8.3 mm● Closed dimension Y ≤ 14.8 mm
Kvs [m3/h]PN class Data sheet 0.25…25 PN 16 N4845 2.5…6.3 0.25…25 0.25…4.0 0.63…25 0.63…25 0.7…14 N4840 N4854 N4845 Retrofitting former Landis &Gyr valves Siemens
Smart Infrastructure 4 A6V12681511_en--_b 2023-05-17 Combinable, programable room automation stations Combinable room thermostats Type DXR2 RXB.. Type RDG.. RDU..
RCU.. AC/DC 24 V; DC 0…10 V DXR2.. RXB39.1.. RDG260, RDG264KN, RDG160T, RDG160KN Detail RDU340 RCU50.. Product documentation Notes Engineering Topic Title Document ID
Mounting and installation Mounting instructions 1) A6V13122035 Standards and directives CE conformity declarations A5W00254962A RCM conformity declaration A5W00254983A
Environmental compatibility Environmental declarations A5W00242127A 1) The mounting instructions are enclosed with the product. Related documents such as the environmental declarations, declarations of conformity, etc., can be downloaded from the following Internet address: www.siemens.com/bt/download
The actuators must be electrically connected in accordance with local regulations (see"Connection diagrams [▶ 13]"). CAUTION National safety regulations Failure to comply with national safety regulations may result in personal injury and property damage.
● Observe national provisions and comply with the appropriate safety regulations. Observe permissible temperatures (see "Technical data [▶ 10]"). The connecting cable of the actuator may come into contact with the hot valve body, provided the temperature of the valve body does not exceed 80 °C.
Siemens Smart Infrastructure 5 A6V12681511_en--_b 2023-05-17 Mounting WARNING● Do not use pipe wrenches, spanners or similar tools.● Avoid lateral pressure or (cable) tension on the mounted actuator!
It is easy to mount the actuator on the valve before commissioning● Remove the protective cover of the valve body.● Position the actuator and tighten the coupling nut manually.● See "Mounting instructions" enclosed with the product package for graphical instructions.
Orientation Installation A [mm]5.5 B [mm]6.0 C [mm]60 Crimp ferrule on stripped wire of connecting cable.● Observe all admissible temperatures (see "Technical data [▶ 10]").
● Do not twist the cable.● Magnets can damage