3341 RWD32 RWD82 Universal Controller For comfort control in HVAC & R-Systems RWD32 RWD82• Standalone electronic temperature controller with P or PI response• Operating voltage in accordance to type AC 230 V or AC 24 V• Control application selectable via Application Number• Active input scale can be selectable
• Two universal inputs for Ni 1000, Pt 1000 temperature sensors &0…10 V signals• Unit can be set as ºC, ºF, % or no specified unit• One 3-position output or two two-position outputs, direct or reverse action• One digital input for day/ night changeover• Entering or changing of all data via operating buttons on the controller, possi-
ble without additional tools• PC connection for downloading canned applications via the software tool Use The universal controllers are intended for Heating, Ventilating, Air-Conditioning and Refrigeration in comfort control plants. It can be mounted in a control panel or in the ARG62.21/ARG62.22 housing on ducts, walls and in plant rooms.
CE2N3341en 03.05.2001 Siemens Building Technologies Landis & Staefa Division HVAC&R Application Functions Summary• Controller Measurement and control of temperature, relative humidity, absolute humidity, en-thalpy, pressure differential, volumetric airflow and indoor air quality. The input scale can be set from –100 units to 8,000 units.
Stand-alone controller with one 3-position or two 2-position (ON / OFF) outputs with independent adjustment on each sequence for direct acting and / or reverse acting. In 3-position operation, the controller exhibits PI response.
• Auxiliary selectable function Universal input X2 for one of the following functions:− PI limiter function (Absolute & Relative)− Remote setpoint function− Cascade control function− Setpoint compensation
− Winter/summer operation− Maximum priority• Digital input D1 for setpoint changeover day / night Input & Output summary Inputs Outputs(either) Operating Type Universal
Digital 3-position 2-position voltage reference 2 2 1 1 1 1 2 2 AC 230 V RWD32 AC 24 V RWD82 Accessories Name Protective small enclosure for wall mounting Protective big enclosure for wall mounting
Software Tool Equipment combinations Type ARG62.21 ARG62.22 S3341A031EN0 Data sheet no. 1846 17... to 19... 1721 / 1748 19... 46... 45... The following Landis & Staefa units can be connected to RWD32 and RWD82 universal controllers.
Units Sensor with LG Ni 1000 temperature sensing element 17... to 19... Sensor with Pt 1000 temperature sensing element Sensor with DC 0...10 V measuring signal
Room temperature sensor with setpoint adjuster QAA25 or QAA25/AP Remote setpoint adjusters FZA21.11 + FZA61.11 Air damper actuators with 3-position input Valve actuators with 3-position input
2/11 Siemens Building Technologies Landis & Staefa Division RWD32/RWD82 Universal controller CE2N3341en 03.05.2001 Other combinations with third-party units are possible, provided the input and output specifications match the RWD32 and RWD82.
A software tool for controller application selection and parameter adjustment is avail-able. It is a user-friendly Windows® 95 (or above) based software tool which provides you a printout of the controller settings.
Software Tool Functions Controller type Main functions The RWD32 and RWD82 are stand-alone universal controllers, which perform both primary and auxiliary control functions. The respective mode is defined by entering the corresponding configuration and setting parameters via the push buttons on the con-
troller or the software tool. The RWD32 and RWD82 controllers can be programmed as follows:• 2-position controller: Q1 and Q2• 3-position controller: Q1 or Q2 reverse or direct acting
reverse and/or direct acting on each step Dependent Control Loops SD SD Setpoint Load Setpoint Load 2 Reverse Acting Sequences (Dependent loops) (Application No.: 10-19)
Independent Control Loops Q2 SD Q1 SD 2 Direct Acting Sequences (Dependent loops) (Application No.: 50-59) Q1 SD Q2 SD ON OFF ON OFF SD SD 2 2 SD SD 2 2 Setpoint
Load SD SD 2 2 SD SD 2 2 Setpoint Load 2 Reverse Acting Sequences (Independent loops) (Application No.: 20-29) 2 Direct Acting Sequences (Independent loops) (Application No.: 60-69)
ON OFF ON OFF ON OFF Reverse and Direct Acting Control Loops Q1 SD Q2 SD SD SD 2 2 SD SD 2 2 Setpoint Load Reverse and Direct Acting Sequences (Application No.: 40-49)
Siemens Building Technologies Landis & Staefa Division RWD32/RWD82 Universal controller 3/11 CE2N3341en 03.05.2001 3-point Control Loop 100%0%6 0 d 1 4 3 3 Load
Setpoint Reverse Acting Sequence (Application No.: 30-39) 100%7 0 d 1 4 3 3 Load 0%Setpoint Direct Acting Sequence (Application No.: 70-79) Universal input X1 Universal input X2
The universal input X1 is used as the primary input for a Landis & Staefa Ni 1000 tem-perature sensor, a Pt 1000 temperature sensor or a 0…10 V DC active input.
The universal input X2 is used as the secondary input for a Landis & Staefa Ni 1000 temperature sensor, a Pt 1000 temperature sensor, an active / passive remote setpoint transmitter or a 0…10 V DC active input.
Digital input D1 The digital input D1 is used to select the day/night changeover. Changeover occurs via potential-free contacts between D1 and M. Digital outputs Q
Each output Q (Q1, Q2) can be configured for either reverse or direct acting. Example Ventilating plant with temperature control Auxiliary functions PI limiter function
Remote setpoint X1 Q1 Q2 Room temperature Heating, reverse action Cooling, direct action Q1 Q1 Q2 Q2 On Off RWD32/82 X1 Temp. 1 0 s 1 4 3 3 One of the following auxiliary functions can be selected:• PI limiter function (Absolute & Relative)• Remote setpoint function• Cascade control function• Setpoint compensation
• Winter/summer operation• Maximum priority Additionally, the day and night operation mode is available. The limiter function with PI control enables abso-lute(or relative) maximum or minimum limitation of the supply air temperature (X2). When the value drops below or exceeds the limiter setpoint, the limiter function controls and takes prior-
ity over the main setpoint. D1 On Off Q1 Q1 Q2 Q2 RWD32/82 X2 X1 Temp. 2 0 s 1 4 3 3 A remote setpoint transmitter (FZA21.11, QAA25 or QAA25/AP), connected to X2 and configured ac-cordingly, enables setpoint adjustment.
Active measurement from 0...10 V DC corresponding adjustable range from –100 to 8000 Passive measurement from 0…1000 Ω correspond-ing adjustable range from –100 to 8000
D1 On Off Q1 Q1 Q2 Q2 RWD32/82 X2 X1 Temp. 3 0 s 1 4 3 3 4/11 Siemens Building Technologies Landis & Staefa Division RWD32/RWD82 Universal controller CE2N3341en 03.05.2001
Cascade control X2 Supply air temperature sensor You can select the PI/PI room/supply air tem-perature cascade control. In this case, the virtual PI room temperature controller determines the setpoint within the limiter setpoints for the PI supply air temperature controller.
Q1 Q2 X2 X1 Y RWD32/82 Temp. 4 0 s 1 4 3 3 Maximum Priority Maximum Priority, cooling If the value (0…10 V) of the input X2 is greater than the calculated output of the 3-point cooling sequence, the output will use the X2 input value as output value.
Q1 Q2 X1 X2 Y RWD32/82 Temp. Setpoint compensation The temperature setpoint X1 is shifted by the tem-perature as measured at sensor X2. Configuration of the RWD32 or RWD82 defines the influence on setpoint X1.
The example shows the room air temperature set-point as controlled by the outside temperature. Q1 Q1 Q2 Q2 On Off RWD32/82 X2 X1 Temp. 6 0 s 1 4 3 3 Winter/ Summer operation
A digital switch or anlog input between terminals X2 and M can be used to implement win-ter/ summer changeover. T Digital changeover When the contact is closed, summer operation is selected. Reverse acting output (Q1 only) is set to direct action (cooling).
Q1 Q1 Q2 Q2 On Off RWD32/82 X2 X1 Temp. 7 0 s 1 4 3 3 Day/ night setpoint Analog changeover When the X2 input exceeds the setpoint, summer operation is selected. Reverse acting output (Q1 only) is set to direct action (cooling).
A contact between terminals D1 and M can be used to implement setpoint changeover for day/ night operation. When the contact is open, the setpoints for day operation are selected.
When the contact is closed, the setpoints for night operation are selected. During the night mode, the following auxiliary func-tions are disabled: remote setpoint, abso-lute/Relative limiter, setpoint compensation and maximum priority.
D1 On Off Q1 Q1 Q2 Q2 RWD32/82 X1 Temp. 8 0 s 1 4 3 3 Siemens Building Technologies Landis & Staefa Division RWD32/RWD82 Universal controller 5/11 CE2N3341en 03.05.2001
Mechanical design Housing Protective housing ARG62.21/ARG62.22 The RWD32 & the RWD82 univers