5536 SEM62.1 SEM62.2 Transformer With housing SEM62.1 SEM62.2 Transformers providing a reduction in voltage from AC 230 V to AC 24 V.· Output power 30 VA· Suitable for mounting on DIN rails· Secondary power supply indication via LED· Integral self-resetting primary fuse· Secondary power supply on/off switch with replaceable fuse
The SEM62.. mains transformers (with housings) reduce an AC 230 V mains voltage to the AC 24 V supply voltage required by the controllers. The transformers have output power ratings of 30 VA. An integral self-resetting fuse on the primary side protects the transformer from overheating. SEM62.2 includes an on/off
switch with replaceable fuse. This eliminates the need for additional 24V circuit on/off switch and fuse (or circuit breaker). Type SEM62.1 SEM62.2 Description Standard transformer Transformer with switch and replaceable fuse
Use Type summary AP1N5536en 2019-03-13 Building Technologies Mechanical design Transformer sizing The SEM62.. transformers are single-phase split-bobbin safety transformer. On the primary side, the transformers are protected by a built-in PTC fuse. If the primary-side fuse trips, the fault condition on the secondary side must be cleared.
When the transformer cools down, the fuse will reset automatically and normal operation will be resumed. Secondary power supply indication is provided via a green LED. SEM62.2 has a secondary side on/off switch with replaceable fuse.
The transformer power can be calculated by adding together the power consumption of all the connected devices. For valves, a figure of 1.5 times the nominal power of the valve should be used. In the case of valves connected in a sequence where only one valve (heating or cooling) can be open at any given time, only the larger valve need be
included in the calculation. Where it is possible for several valves to be open at the same time, the nominal power of all connected valves must be added together.
Example 1 controller 1 valve actuator (heating) 1 valve actuator (cooling) ( x 1.5) 2 VA 8.5 VA Total 4 VA– VA 13 VA 17 VA Mounting / installation notes The transformer can be mounted as follows: Observe all local installation and mounting regulations.
A B C On a DIN rail (EN 50 022-35 x 7.5) at least 120 mm long Flat surface mounted with 2 screws Front mounted using standard elements e.g. 1x DIN rail 150 mm long, 2 x hexagonal placeholders 50 mm, washers and screws
D In ARG62.22 protective housing with other devices The SEM.. is for indoor use and must have all terminations well-protected by plastic cover or in a panel/enclosure.
A B C D 2/4 Siemens Building Technologies SEM62… Transformer AP1N5536en 2019-03-13 Electrical installation The SEM62.. is designed for AC 230 V primary supply voltage.
When using several transformers in one system, the connection terminals G0 must be galvanically connected. There must be a minimum of 8mm distance from terminations to panel/enclosures in order to avoid electric shock. The on/off switch is for secondary power supply only. Under no circumstances should the front cover of SEM.. be
removed. All local electricity regulations must be observed. The device is considered electrical and electronic equipment for disposal in terms of the applicable European Directive and may not be disposed of as domestic garbage.
· Dispose of the device through channels provided for this purpose.· Comply with all local and currently applicable laws and regulations. Disposal Technical data
General data Power supply Primary electrical data Secondary electrical data Voltage Frequency Power consumption Fuse Voltage (Safety Extra Low Voltage) Total output power Nominal current Fuse rating Fuse dimension
Temperature range Contamination level Operation Storage Ambient humidity RCM conformity Standards and directives EU Conformity (CE) Terminals Screw terminals for cables with
Weight (Including packaging) SEM62.1 SEM62.2 Dimensions (W x H x D) Mounting General ambient conditions Orientation Conditions of use AC 230 V –15…+10 %50 Hz/60 Hz
Max. 200 mA self-resetting (PTC). AC 24 V (SELV) 30 VA 1.25 A Time lag 1.6 A low breaking capacity 5 mm dia x 20 mm long (wire inside glass type) 0...50 °C– 25...70 °C Max. 65 %rh, non-condensing
Normal contamination CE3T5536xx *) CE3T5536en_C1*) Min. 0.5 mm dia. Max. 2 x 1.5 mm2 or 2.5 mm2 0.900 kg 0.910 kg 113.8 x 106 x 56.4 mm Snap-mounted on rail type EN50022-35 x 7.5 or screwed to a flat surface Any
– For internal use, in control panels etc.– Up to 2000 m above sea level*) The documents can be downloaded from http://siemens.com/bt/download. Siemens Building Technologies
SEM62… Transformer 3/4 AP1N5536en 2019-03-13 N L SEM62... G0 G G0 G Legend N, L AC 230 V Input G0, G AC 24 V output Diagrams Internal diagram Dimensions Note: Total transformer output power is 30VA. Two sets of GO, G terminals are provided for easier wiring
purposes. All dimensions in mm Issued by Siemens Switzerland Ltd. Building Technologies Division International Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58 724 2424 www.siemens.com/buildingtechnologies
4/4 Siemens Building Technologies SEM62… Transformer© Siemens Switzerland Ltd, 2002 - 2019 Technical specifications and availability subject to change without notice.